How does the clean room detect wind volume and wind speed?

1. The wind speed detection must first be carried out. The effects of purifying the air conditioner must be obtained under the designed wind speed .
2. Before the air volume test, it must be checked whether the fan is running normally, whether the components in the system are installed correctly, and it is barrier-free (such as whether the filter is blocked or blocked). All valves should be fixed at a certain open position and must be actually measured. The measured air outlet and duct size.
3. For the unidirectional flow (laminar flow) clean room , the air supply volume is determined by the method of the average cross-sectional wind speed and cross-sectional area of ​​the chamber. The measured cross-sectional area of ​​the vertical unidirectional flow (laminar flow) clean room is 0.8 m from the ground. Horizontal section, horizontal unidirectional flow (laminar flow) clean room takes a vertical section of 0.5m from the air supply surface. The distance between the measuring points on the section should not exceed 2m, and the number of measuring points should be no less than 10, evenly arranged. The instrument uses a hot ball anemometer .
4. For the turbulent clean room, the air supply method or the air duct method is used to determine the air supply volume.
5. For the tuyere without filter installed, it can be carried out according to the current national standard "Code for Construction and Acceptance of Ventilation and Air Conditioning Engineering" GBJ243 Appendix 1.
6. For the tuyere with the filter, the auxiliary duct can be selected according to the tuyere form, that is, the straight pipe section which is made of the hard plate and has the same length as the air inlet, and the length is equal to 2 times of the tuyere side, is connected to the outside of the filter tuyere. On the exit plane of the auxiliary duct, the measuring points are uniformly arranged according to the number of points measured by zui, and the speed of each point is measured by a hot ball anemometer. The air volume is determined by the net cross-sectional area of ​​the average wind speed of the tuyere section.
7. For the air outlet with the same diffusion plate, the air volume can be detected according to the diffused air volume resistance curve (factory air volume resistance curve or field measured air volume resistance curve) and the measured diffusion plate resistance (the difference between the hole plate and the indoor pressure). . The measurement should be carried out with a micro-pressure gauge and a micro-management, or with a fine rubber instead of a sub-management, but the plane of the hole should be parallel to the direction of the gas flow. In addition, other methods approved by the professional testing department may be used.
8. When there is a long branch pipe section on the windward side of the tuyere and the hole has been or can be punched, the air volume can be determined by the air duct method. The distance between the section and the local resistance component is determined. The former resistance component is not less than 3 times the diameter or the length of the 3 times of the large side, and the latter is not less than 5 times the diameter or 5 times the length of the large side.
9. For the rectangular duct, the measured section is divided into several equal small sections, each small section is as close as possible to the square, the side length is not more than 200mm, and the measuring point is set at the center of the small section, but the number of measuring points on the entire section is not suitable. Less than three. For circular ducts, the cross section should be divided according to the equal area ring method and the number of measuring points should be determined.
Holes are made in the outer wall of the duct for insertion into the hot ball anemometer pole or Pitot tube. When using Pitot, the dynamic pressure is measured first, and then the air volume is determined by the following formula:
Q=1.29 F
Pa={(++)/n}2
Q----wind volume, m3/s
F----pipe cross-sectional area, m2
Pd1...Pdn----dynamic pressure at each point, Pa.

Shanghai Sujing Industrial Co., Ltd.
  
If you have any needs, you can always pass with me, thank you very much for your support to Sujing, look forward to working with you.
  
have a pleasant workday!
  
Thankyou&Bestregard!
  
SUJING—JINGHUA

Vegetable & Fruit Powder

Increasing the dietary consumption of fruits and vegetables is a worldwide concern, making it a unique opportunity for food & beverage producers. Enriching products with real fruit and vegetable content makes them healthier and instantly increases their overall appeal. Manufactured from carefully selected raw materials and processed using unique drying technologies, our dehydrated fruits and vegetables are tasty, colorful, safe, and easy to use. Our offer includes 100% fruit and vegetable powders that contain no carriers and comply with both baby food and organic standards.

Vegetable Powder,Fruit Powder,Air Dried Organic Beetroot Powder,Organic Beets

Organicway (xi'an) Food Ingredients Inc. , https://www.organicwayince.com